DRL-48V240W1EN Hikvision Industrial Power Supply Unit
- DIN rail
- Compliance to SEMI F47 @ 200Vac, DOE VI Energy Standard
RRP RM387.00
Features
- Universal AC input voltage range, Integrated constant current circuit for reactive loads, High power density, Decreased no-load power consumption
- output 48V, 5.0A, 240W
- Operate from -30C to +70C w/ -40C Cold Start
Specifications
Input Ratings / Characteristics
- Nominal Input Voltage
- 100-240Vac
- Input Voltage Range
- 90-264Vac
- Nominal Input Frequency
- 50-60Hz
- Input Frequency Range
- 47-63Hz
- Input Current
- 2.5A typ. @ 115Vac, 1.3A typ. @ 230Vac
- Efficiency at 100% Load
- 90.5% typ. @ 230Vac
- Average Efficiency (25%, 50%, 75%, 100%)
- 88% typ. @ 115Vac
- No Load Power Consumption
- 0.3W max @ 115Vac & 230Vac
- Max Inrush Current (Cold Start)
- 40A typ. @ 230Vac
- Power Factor at 100% Load
- > 0.95 @ 115Vac & 230Vac
- Leakage Current
- < 0.75mA @ 240Vac
Output Ratings / Characteristics
- Nominal Output Voltage
- 48Vdc
- Factory Set Point Tolerance
- 48Vdc ± 1%
- Output Voltage Adjustment Range
- 43.2-52.8Vdc
- Output Current
- 5.0A
- Output Power
- 240W max
- Line Regulation
- ± 0.5% @ 115Vac & 230Vac
- Load Regulation
- ± 0.5%
- PARD*3 (20MHz)
- < 200mVpp @ 0°C to +70°C
< 600mVpp @ -30°C to 0°C - Rise Time
- 30ms typ. @ 115Vac & 230Vac
- Start-up Time
- 500ms typ. @ 115Vac & 230Vac
- Hold-up Time
- 20ms typ. @ 115Vac (100% load)
20ms typ. @ 230Vac (100% load) - Dynamic Response (Overshoot & Undershoot O/P Voltage)
- ± 10% @ 115Vac & 230Vac input, 10-100% load
(Slew Rate: 2.5A/μS, 50% duty cycle @ 5Hz & 10KHz) - Start-up with Capacitive Loads
- 3,000µF Max
Mechanical
- Case Cover / Chassis
- SGCC/ Aluminum
- Dimensions (L x W x D)
- 123.6 x 40 x 117.2 mm (4.87 x 1.57 x 4.61 inch)
- Unit Weight
- 0.62 kg (1.37 lb)
- Indicator
- Green LED (DC OK)
- Cooling System
- Convection
- Terminal*4
- Input 3 Pins (Rated 300V/30A)
Output 4 Pins (Rated 300V/20A) - Mounting Rail
- Standard TS35 DIN Rail in accordance with EN 60715
- Noise (1 Meter from power supply) Sound Pressure Level (SPL)
- < 25dBA
Environment
- Surrounding Air Temperature
- Operating -30°C to +70°C (-40°C Cold Start)
Storage -40°C to +85°C - Operating Humidity
- 20 to 90% RH (Non-Condensing)
- Operating Altitude
- 0 to 5,000 Meters (16,400 ft.)
Protections
- Overvoltage
- <64.8V, SELV Output, Latch Mode
- Overload / Overcurrent
- 105 - 150% of rated load current, Auto-recovery
- Over Temperature
- Latch Mode
- Short Circuit
- Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Reliability Data
- MTBF Telcordia SR-332
- > 700,000 hrs
- Expected Cap Life Time
- 10 years (230Vac, 50% load @ 40°C)
Galvanic Isolation
- Input to Output
- 3.0KVac
- Input to Ground
- 2.0KVac
- Output to Ground
- 1.0KVac